Customization: | Available |
---|---|
Cylinder Volume: | 40L, 70L, 90L, 100L, 120L, 150L, 180L |
Capacity of Gas: | 38kg;53kg;75kg;69kg;82kg;104kg;120kg |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
• Cabinet automatic HFC-227ea/FM200(Heptafluoropropane) fire suppression system uses the solenoid valve as the starting mode with the elegant appearance design. The cylinder is placed in the cabinet. For different protection zone, according to the different volume zone to match different size cylinder, which can reduce the occupied area.
• According to different volume size, different extinguishing agent, different starting mode to assemble.
• Independent sets, flexible installation, good appearance.
• Without cylinder room, can install in the protection zone, handy and romovable.
• Automatic HFC-227ea/FM200(Heptafluoropropane) fire extinguishing system is a set of fire extinguishing, automatic control and fire detection in one system which is the modern intelligent automatic fire extinguishing device.
• HFC-227ea/FM200 (Heptafluoropropane) is a kind of colourless, tasteless, not conduct electricity and no secondary pollution gas. It belongs to a kind of clean extinguishing agent.
• The ozone-depleting potential value is zero.
• Cleanness, low toxicity, good electrical insulation, higher fire extinguishing efficiency.
• It is currently an ideal substitute for the halon extinguishing agent.
NO. | Specifications | Parameters |
1 | Cylinder capacity | 40Ltr,70Ltr,90Ltr,100Ltr, 120Ltr,150Ltr,180Ltr |
2 | Device model | GQQ40/2.5, GQQ70/2.5, GQQ90/2.5, GQQ100/2.5, GQQ120/2.5, GQQ150/2.5, GQQ180/2.5 |
3 | Filling pressure | 2.5Mpa |
4 | Max filling rate | 0.95kg/L |
5 | Discharge time | ≤10s |
6 | Working temperature | 0ºC~50ºC |
7 | Max working pressure | 4.2Mpa |
8 | Discharge pressure | 5.6±0.28Mpa |
9 | Proportion of protected zone | ≤500m² |
10 | Volume of protected zone | ≤1600m³ |
11 | Actuation | Automatic or manual start |
Specification | Size(mm) | Volume(cbm) | Net weight (kg) |
GQQ40/2.5 | 450*400*1450 | 0.261 | 39 |
GQQ70/2.5 | 550*450*1650 | 0.408 | 53 |
GQQ90/2.5 | 550*450*1650 | 0.408 | 75 |
GQQ100/2.5 | 550*450*1650 | 0.408 | 69 |
GQQ120/2.5 | 550*550*1900 | 0.575 | 82 |
GQQ150/2.5 | 550*550*1900 | 0.575 | 104 |
GQQ180/2.5 | 600*550*2150 | 0.71 | 120 |
Cabinet fm200 system: management of big zone, simple integration, direct spraying effect in protection zone, efficient fire suppression.
1. Effective firefighting in relatively small region
2. Simple assembly of device without pipeline
3. No extra space to store device